Use:
Validates proper generator behavior after the EI system has been fully commissioned.
Please contact our Customer Success team if you have any questions about this procedure:
Phone: +1 408 402-0802
This procedure tests the generator's auto-start, auto-stop, manual-start, and manual-stop settings.
If you are using a manual-start generator, perform only steps 1 and 2.
Preliminary:
EI App:
- Open the Tigo EI App and tap the gear in the lower right corner.
- Tap Generator Management > Generator Mode
Grid power:
Turn off the grid power to the Tigo ATS
- The ATS will shift to backup mode.
- The Tigo Inverter and Battery will also switch to backup mode.
- The house will now be running on solar and battery power.
STEP 1 Test Generator Manual Start
|
1. Select Generator Mode ON The generator will start after a short delay. Attention! If you manually start the generator, then you must manually stop it. Although the generator will stop charging the batteries at 95%, it will keep running until you shut it off. |
STEP 2 Test Manual Stop
|
1. Allow the generator to run for at least 5 minutes from the previous step. 2. Select PAUSE to stop the generator. 3. Once the generator stops, continue to Step 3. |
STEP 3 Test Generator Auto Start
|
1. Verify the operating mode is set to AUTO. 2. Depending on the battery SOC during commissioning, it may be necessary to start large loads to discharge the battery faster than normal. 3. Verify the generator automatically starts at 20% SOC. 4. Leave the generator running and verify energy flow using the EI App. Attention! If you manually start the generator, then you must manually stop it. |
STEP 4 Verify Generator Energy Flow While Generator is Running
|
1. Return to the EI App main page 2. Verify that the generator power is going to the loads (arrows to house icon) and to the battery (arrows to battery icon). 3. The battery state of charge should increase over time. Attention! Notice how the energy flow shows no flow from the Inverter to the Home. This is because the Generator powers the loads, and the remaining generator power charges the battery. This is normal behavior. |
STEP 5 Test Generator Auto Stop
|
1. The generator should still be running from the previous step. 2. Allow the state of charge to increase to 95%. 3. The generator should automatically stop at this high SOC limit. 4. Set the mode to AUTO for normal operation. |
If the system behaves abnormally during these tests, manually stop the generator and perform the necessary troubleshooting.
Troubleshooting
| Issue | Solution |
| The generator will not auto start |
|
| The generator will not charge the batteries |
|
Figure 1