| 1 |
The number of Gateways communicating with the data logger does not match the amount specified on the Equipment page. |
| Checks: |
- Verify that the number of Gateways installed matches the amount entered on the Equipment page. If necessary, correct the number of Gateways installed.
- If you configured your system using its web page, you can view the number of gateways configured using the Equipment page.
- If you configured the system via the Tigo SMART App, click 'back' until you see a page asking how many modules and gateways there are.
- Check Gateway wiring and termination if the numbers match but the error persists.
|
| 2 |
Problem communicating with Gateway |
| Checks |
- Check Gateway wiring and termination
- The terminating resistor should be installed on the last Gateway in the chain
- Older Gateways need to have the jumper set inside (last Gateway only)
|
| 3 |
Problem communicating with Gateway |
| Checks |
- Check Gateway wiring and termination
|
| 4 |
Problem communicating with Gateway |
| |
- Check Gateway wiring and termination
|
| 5 |
No available wireless channel for Gateway |
| |
|
| 6 |
Problem communicating with Gateway |
| |
- Check Gateway wiring and termination
|
| 7 |
Problem communicating with Gateway |
| |
- Check Gateway wiring and termination resistor installed only on the last gateway.
- Use proper cable: either Rs-485 or Ethernet. It must be a twisted pair with at least two pairs.
|
| 8 |
Problem communicating with Gateway |
| |
|
| 9 |
Problem communicating with Gateway |
| |
|
| 10 |
Problem communicating with Gateway |
| |
|
| 11 |
Discovery incomplete - lost communication between Gateway and smart modules |
| |
- Check proximity to modules, 50 feet radius recommended, 110 feet maximum for MESH
- Check the RSSI map via laptop or smartphone to verify that all units have RSSI of at least 80 (RSSI = Radio Signal Strength Indicator). If you see a dark blue and grey area on your RSSI map, it's a good indication that you should improve the Gateway position or add additional Gateways.
- Check Gateway wiring and termination.
- Ensure that all smart modules are powered on, and allow enough time for Discovery to complete before sunset
|
| 12 |
Problem communicating with Gateway |
| |
|
| 13 |
Discovery incomplete - lost communication between Gateway and smart modules |
| |
- Same as #7
- Ensure that all smart modules are powered on, and allow enough time for Discovery to complete before sunset
|
| 14 |
No available wireless channel for Gateway |
| |
- Call Tigo technical support for advanced troubleshooting. Click here for contact information
|
| 15 |
No available wireless channel for Gateway |
| |
- Call Tigo technical support for advanced troubleshooting. Click here for contact information
|
| 16 |
Problem communicating with Gateway |
| |
- Check Gateway wiring and termination
|
| 17 |
Discovery finished but found no modules |
| |
- Check proximity to modules and run Discovery during daylight hours by starting early after sunrise.
|
| 18 |
Minor Discovery error |
| |
- Restart Discovery from Tigo SMART App or Cloud Connect
|
| 19 |
Minor Discovery error |
| |
- Restart Discovery from Tigo SMART App or Cloud Connect
|
| 20 |
Problem communicating with Gateway |
| |
|
| 21 |
Problem communicating with Gateway |
| |
|
| 22 |
Problem communicating with Gateway |
| |
|
| 23 |
Configuration file missing or incomplete |
| |
- Verify that optimizer serial numbers were entered on the System Layout page
- Go to 'My Installations' and under 'Pending Systems' find your site and press 'Configure'. Go to 'System Mapping' and make sure you have all the barcodes entered correctly; no typos or empty spaces. Also notice that MAC IDs must be exactly 16 characters long for Long Format, and contain only the digits 0-9 and uppercase letters A-F. Once done hit 'Save' and restart discovery on the CC using the Tigo SMART App or the LCD menu options: 2. control > 1. discovery.
|
| 24 |
Lost communication with Gateway |
| |
- Same as #7
- Restart Discovery
- If the error happens 2 or more times, submit a ticket Click here for support information
- Restart discovery on the CC using the Tigo SMART App or the LCD menu options: 2. control then 1. discovery
|
| 25 |
Lost communication with Gateway |
| |
- Same as #7
- If the error occurs 3 or more times: Click here for support information
|
| 26 |
Lost communication with Gateway |
| |
- Same as #7
- Restart Discovery and call Tigo technical support for advanced troubleshooting if the error persists. Click here for support information
|
| 27 |
Problem communicating with Gateway |
| |
|
| 28 |
Optimizer bar code(s) entered incorrectly resulting in Invalid Serial Number |
| |
- Verify system configuration by using Layout Page to compare with barcode stickers pulled at installation
- Long Format Serial numbers/MAC addresses must be exactly 16 digits and contain only the digits 0-9 and uppercase letters A-F, and there is no software error checking upon entry.
|
| 29 |
Optimizer bar code(s) entered incorrectly |
| |
|
| 30 |
Duplicate optimizer panel label(s), same serial was entered twice. |
| |
|
| 31 |
Duplicate optimizer panel label(s) |
| |
|