This article reveals the recommended resolution for common system faults, inverter warnings, and inverter faults. A full downloadable code document (showing all codes and faults), is attached at the bottom of this article.
Important: Only qualified people should perform the suggestions and recommended actions below. Always consult your installer.
Inverter Warning Codes
Code |
Description |
Suggestion |
203 |
PV1 or PV2 Circuit short |
1. Check the PV panel polarity. |
204 |
Disconnect function abnormal |
1. Shut down the system. |
205 |
PV1 or PV2 boost broken |
1. Restart the inverter. |
207 |
USB over-current |
1. Unplug the USB disk or monitor. |
401 |
Inverter to Energy Meter abnormal communication |
1. Check if the meter is on. |
404 |
EEPROM abnormal |
1. Restart the inverter. |
405 |
The firmware version is not consistent |
Update inverter to the latest firmware version. |
412 |
Grid-Connected Startup Condition Abnormal |
This can be related to a number of things, but mostly wiring issues. Other causes could be grid voltage high or low out of spec from the EI Inverter firmware settings. |
607 |
ATS Communication Fault |
The RS-495 wire between the 200A ATS and the EI Inverter is miswired. Use the QSG to verify connection. |
Inverter Fault Codes
Code |
Description |
Suggestion |
402 |
Output High DCI |
1. Restart the inverter. |
404 |
Bus sample fault |
1. Restart the inverter. |
405 |
Relay fault |
1. Restart the inverter. |
408 |
Over Temperature |
1. If the ambient temperature of the inverter is lower than 60°C, restart the inverter. |
409 |
Bus overvoltage String voltage has exceeded 550VDC |
1. Restart the inverter. |
411 |
DSP communicates M3 abnormal |
1. Restart the inverter. |
414 |
EEPROM fault |
1. Restart the inverter. |
417 |
The data sampled by the |
1. Restart the inverter. |
420 |
GFCI fault |
1. Restart the inverter. |
607 |
EPS Abnormal |
Inverter experienced too high of a current draw while in Backup Mode. |
System Fault Codes
Code |
Error message |
Description |
Suggestion |
201 |
Residual I High |
Leakage current too high |
1. Restart the inverter |
202 |
PV Voltage High |
The DC input voltage is exceeding the maximum tolerable value. |
1. Disconnect the DC switch immediately. |
203 |
PV Isolation Low |
Insulation problem |
1. Check if the panel enclosure is grounded properly. |
300 |
AC V Out range |
The utility grid voltage is out of permissible range. |
1. Turn off the inverter DC switch. |
302 |
No AC connection |
No AC connection The inverter does not detect grid voltage. |
1. Check AC wiring connections. |
303 |
PE abnormal |
Neutral and PE voltages exceed 30V |
1. Check the voltage of Neutral and PE |
304 |
AC F Out range |
Utility grid frequency out of permissible range. |
1. Please switch off the DC switch |
407 |
Auto Test Failed |
The EI inverter initial Autotest has failed |
1. Restart inverter. |
500 |
BMS COM Fault |
BMS not able to communication properly with the inverter. | 1. Check RS485 cable connection. 2. Check if the battery is sleeping. 3. If error still exists, contact Tigo Support. |